Line Mini-Split Heat Pump Series
41 codes
/
Fault

F1 Module Protection Error

LED

What it means

The power module directly drives the compressor. When it detects overcurrent, overvoltage, or overheat, it stops the compressor and sends a shutdown request to the module panel. The resulting error is called module protection error. L-codes (L0–LC) are subdivided failures of F1 — see those entries for specific subcategory names and primary parts.

Inspection path

1 Supply voltage 2 Compressor wire and reactor wire 3 System pressure 4 Module panel 5 Main external control panel 6 Compressor

Diagnostic procedure

  1. Check if the compressor wire order is correct. If wired in reverse, try swapping the U-V phase wires to see if the error clears.
  2. Verify supply voltage stability. Measure system pressure — high pressure can cause compressor rotation problems.
  3. Confirm the module panel is firmly mounted to the radiator for adequate cooling. Check if indoor or outdoor heat exchangers are dirty, which causes poor heat transfer and elevated system pressure.
  4. If the error appears immediately on startup, a physical component failure is likely (unrelated to voltage or pressure). Inspect for strike-arc damage near the module panel. Use a multimeter to confirm equal resistance between any two compressor wires — should be ohm-level and equal across all pairs. Use a megameter to verify insulation resistance of each compressor wire to earth (should be MΩ level). Check that the reactor wire is firmly connected and the reactor is not damaged.
  5. Test that the 15V and 5V (or 3.3V) power supplies on the module panel are stable. Rule out power supply issues originating from the main external control panel.
  6. Using the diode function on the multimeter, test the power module: measure P against U, V, and W — one direction should show infinite resistance, the other a fixed on-state voltage (typically ~0.5V). Repeat for N against U, V, and W. A short circuit in any measurement indicates a damaged power module.
  7. Replace the module panel with a known-good unit. If the unit runs normally after replacement, the original module panel is damaged.
  8. After ruling out module, wiring, system, and power supply issues, listen to the compressor. If only electromagnetic sound is present without the compressor starting, or if the compressor runs irregularly then shuts down and indicates error, the compressor may be blocked or damaged.

Tools

  • Multimeter
  • Pressure gauge
  • Megameter
  • Module panel in normal working condition

Frequent parts

  • Supply voltage
  • Compressor wire
  • Reactor
  • Module panel
  • Main external control panel
  • Compressor

Related codes

Safety Disconnect power at the breaker before opening any access panel. DC bus capacitors retain charge for up to 5 minutes after disconnect — verify with a meter before touching live components.
Sensor Reference 6

Recirculated

20 kΩ @ 25°C
Too-high resistance Incorrect back temperature value affects electronic expansion valve adjustment and four-way valve position confirmation during heating.
Too-low resistance Incorrect back temperature value affects electronic expansion valve adjustment and four-way valve position confirmation during heating.

External temperature

15 kΩ @ 25°C
Too-high resistance Detected outdoor temperature reads lower than actual, causing incorrect temperature-based control decisions.
Too-low resistance Detected outdoor temperature reads higher than actual, causing incorrect temperature-based control decisions.

Exhaust

50 kΩ @ 25°C
Too-high resistance Detected exhaust temperature reads lower than actual. The system may fail to activate protection when exhaust temperature is genuinely dangerous.
Too-low resistance Detected exhaust temperature reads higher than actual. The unit enters high exhaust temperature protection frequently, compressor frequency threshold rises, leading to unwanted shutdowns. Example: installing a 20KΩ coil sensor in place of the 50KΩ exhaust sensor produces this behavior.

Internal coil

20 kΩ @ 25°C
Too-high resistance Detected temperature reads lower than actual. May cause high-pressure cold-blast protection during heating or frequent anti-freezing protection during cooling.
Too-low resistance Detected temperature reads higher than actual. May cause frequent overheat protection during heating or overload protection during cooling.

External coil

20 kΩ @ 25°C
Too-high resistance Detected temperature reads lower than actual. May cause frequent entry into defrost mode, illusory defrost cycles, or protection errors during cooling.
Too-low resistance Detected temperature reads higher than actual. May cause defrost failures during heating or protection activation during cooling.

Internal temperature

15 kΩ @ 25°C
Too-high resistance Detected temperature reads lower than actual. May cause shutdown errors in heating mode or startup failures in cooling mode.
Too-low resistance Detected temperature reads higher than actual. May cause startup errors in heating mode or shutdown failures in cooling mode.