Fault
FA Recirculated Sensor Error
LED
What it means
Applies only to models with electronic expansion valves. The recirculated sensor back temperature is used for electronic expansion valve adjustment and to confirm the four-way valve has changed position during heating. When the main control panel detects an open circuit or short circuit on this sensor, it raises this error.
Inspection path
1 Four-way valve → 2 Recirculated sensor → 3 Sensor wire → 4 Connectors → 5 Main external control panel
Diagnostic procedure
- If the error appears in heating mode but not cooling mode, first check whether the four-way valve failed to change position or is experiencing backflow — estimate via high and low pressure readings. For electrical confirmation during heating: verify the four-way valve terminal switches a 220V circuit. If 220V is present but the valve still fails to change position, the four-way valve is faulty. If 220V is absent in heating mode, the main external control panel is faulty.
- If the four-way valve is not the issue, measure sensor resistance (should be approximately 20KΩ at 25°C). Check for short circuit or open circuit.
- Verify all terminal connectors are firmly seated. Check for loose solder joints.
- Check whether the sensor has moisture damage, especially if the sensor lead is routed above the copper pipe.
- Replace the suspect recirculated sensor with a known-good unit. If the error clears, the original sensor is faulty. If the error persists, replace the main external control panel.
Tools
- Multimeter
- Pressure gauge
- 20KΩ recirculated sensor in normal working condition
Frequent parts
- Four-way valve
- Recirculated sensor
- Main external control panel
Sensors referenced
Safety
Disconnect power at the breaker before opening any access panel. DC bus capacitors
retain charge for up to 5 minutes after disconnect — verify with a meter before
touching live components.